Plate Heat Exchanger Troubleshooting Guide
A comprehensive guide for common faults, causes, and solutions in plate heat exchangers used in HVAC and industrial heating systems. Improve efficiency, reduce downtime, and extend equipment lifespan.
Plate heat exchanger units are widely used in HVAC and industrial heating systems. During operation, various issues may occur. Regular inspection and maintenance can improve system efficiency, extend equipment lifespan, and reduce operational costs.
Contact Engineering Team on WhatsApp
Common Faults and Solutions
1. Fault Indicator Light is ON
Cause: Motor current exceeds rated value, thermal relay protection activated.
Solution: Press the reset button and wait for relay to cool before resetting.
2. System Has Pressure but Gauge Shows 0
Cause: Needle valve connected to pressure gauge is closed.
Solution: Ensure all needle valves are fully open during operation.
3. Secondary Side Overpressure
Cause: Water expansion after temperature rise increases system pressure.
Solution: Release air and drain water; pressure stabilizes as temperature stabilizes.
4. How to Identify Filter Blockage
- Primary Side: Large temperature difference, secondary not heating. Check and clean filter.
- Secondary Side: Large temperature difference in secondary loop, low pressure difference. Check and clean filter.
5. How to Identify Heat Exchanger Blockage
Symptoms: ΔP > 0.15 MPa, secondary supply temperature low.
Solution: Disassemble and clean the heat exchanger.
6. System Not Heating
Primary Side Issues: Insufficient flow, valves not fully open, filter blockage. Check valves, clean filters. Adjust flow according to ΔP.
Secondary Side Issues: Poor circulation, blocked filters, heat exchanger blockage. Check circulation, clean filters, and disassemble exchanger if necessary.
7. Make-up Water Cannot Enter System
Symptoms: Pump running but pressure not increasing.
Cause: Air trapped in system.
Solution: Perform air venting.
8. Variable Frequency Make-up System Not Working
Check switch is set to Auto/Variable Frequency and pump is running (green light ON). Check inverter alarm codes: “F” = Fault → reset; “R” = Warning → does not affect operation.
9. Secondary Supply Temperature Too High
Solution: Throttle primary supply valve, keep return valve fully open.
10. Excessive Pump Noise
Causes: Mechanical wear, air in pump, loose components.
Solution: Vent the pump, check fan cover, perform regular maintenance (lubrication, parts replacement).
11. Frequent Make-up Water & Pressure Drops
Possible Causes: Leakage in secondary system, faulty check valve.
Solution: Inspect pipelines and valves, replace leaking check valve.
12. One Pump Runs, the Other Rotates Backward
Cause: Check valve failure → backflow.
Solution: Replace check valve, temporarily close inlet/outlet valves.
13. How to Check Pump Rotation Direction
Use a clamp meter. Correct rotation = higher current than reverse rotation.
14. Pump Indicator ON but Pump Not Running
Solution: Check circuit breakers in control cabinet; ensure all breakers are switched ON.